2015-04-30 15:46:35 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT:15030955 |
| ADD: 400 N. FLAGLER SUITE: 803 |
| CONT: MARYJULI |
| TEL: (561)386-6032 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| NOTICE!!!!!!!!!!! NOTICE!!!!!!!!!!!!!: CHAPTER |
| 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL |
| GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| |
| |
| 2ND REVIEW |
| DATE: THURS. APRIL 30/ 2015 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST, THE DESIGNER OF RECORD HAS NOT REVIEWED |
| THE PRODUCT APPROVAL AND PUT THEIR SHOP DRAWING STAMP |
| OF APPROVAL. |
| SHEET 1 INDICATES NEW SLIDING GLASS DOORS:2010 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS |
| & CLADDING, NO APPROVALS SUBMITTED. |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| |
| 2) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) SHEET A1 INDICATES THE WIND DESIGN, NOTE THIS IS A |
| 225 FT HIGHRISE BUILDING WITH A D EXPOSURE, THE |
| PRESSURES STATED ON THE PLANS APPEAR TO BE FOR 60 FT. |
| ABOVE GRADE, D EXPOSURE. NEGATIVE PRESSURES ARE TAKEN |
| FROM THE ROOF, PLEAS PROVIDE CALCULATIONS ON HOW THESE |
| PRESSURES WERE DERIVED. THE UNIT FLOOR PLAN IN RELATION |
| TO THE BUILDING CAN NOT IDENTIFY IF THIS IS IN A END |
| ZONE(ZONE # 5) OR INTERIOR ZONE (ZONE # 4). |
| |
| 4) 2ND REQUEST. SUBMITTED IN WITH THE PLANS IS |
| DOCUMENTS FOR FLOOR INSULATION PROFLEX 90 FLOOR |
| INSULATION, PLEASE NOTE THERE WERE A FEW PERMITS ISSUED |
| WITH THIS PRODUCT BUT IT HAS BEEN BROUGHT TO OUR |
| ATTENTION THIS REPORT WITH A INSULATION CLASS OF IIC 72 |
| IS WITH A DROPPED CEILING. THE PRODUCT IS TO BE TESTED |
| WITH FLOOR TILE, THIN-SET, INSULATION MATERIAL AND 6 |
| INCH THICK CONCRETE SLAB. SEE THE FOLLOWING CODE |
| REQUIREMENTS, THE FULL TEST DOCUMENTS REQUIRED. |
| |
| 4A)PLEASE NOTE THE PROFLEX TEST SUBMITTED FOR THE ASTM |
| E 492 FOR THE IIC RATING OF 68 BD IS WITH A DROP |
| CEILING AND 3 1/2 INCHES OF INSULATION. THE TEST |
| SUBMITTED ASTM E-90 FOR THE STC RATING OF 72 DB ALSO |
| HAS A DROPPED CEILING, 10 PLENUM, 3 1/2 INCHES OF |
| INSULATION. THE TEST HAVE TO BE WITH A 6 INCH SLAB AND |
| NO DROPPED CEILING. |
| |
| 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 4D) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 703.4 NONCOMBUSTIBILITY TESTS. |
| THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 703.4.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 703.4.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |
| |