2015-03-26 06:38:18 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT:15030955 |
| ADD: 400 N. FLAGLER SUITE: 803 |
| CONT: MARYJULI |
| TEL: (561)386-6032 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1ST REVIEW |
| DATE: THURS. MARCH 26/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET 1 INDICATES NEW SLIDING GLASS DOORS:2010 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS |
| & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) WITH THE NEW WINDOWS AND SLIDDING GLASS DOORS THE |
| PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA; |
| WIND DESIGN CRITERIA |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| |
| |
| 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| 4) SUBMITTED IN WITH THE PLANS IS DOCUMENTS FOR FLOOR |
| INSULATION PROFLEX 90 FLOOR INSULATION, PLEASE NOTE |
| THERE WERE A FEW PERMITS ISSUED WITH THIS PRODUCT BUT |
| IT HAS BEEN BROUGHT TO OUR ATTENTION THIS REPORT WITH A |
| INSULATION CLASS OF IIC 72 IS WITH A DROPPED CEILING. |
| THE PRODUCT IS TO BE TESTED WITH FLOOR TILE, THIN-SET, |
| INSULATION MATERIAL AND 6 INCH THICK CONCRETE SLAB. SEE |
| THE FOLLOWING CODE REQUIREMENTS, THE FULL TEST |
| DOCUMENTS REQUIRED. |
| |
| 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 703.4 NONCOMBUSTIBILITY TESTS. |
| THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 703.4.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 703.4.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |