2015-04-26 08:17:57BUILDING PLAN REVIEW
 W. P. B. PERMIT:15030954
 ADD: 400 N. FLAGLER SUITE: 2305
 CONT: MARYJULI
 TEL: (561)386-6032
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: SUN. APRIL 26/ 2015
 ACTION: DENIED
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION. THIS CAN BE PUT ON EITHER THE DESIGN
 PROFESSIONAL AND OR THE CONTRACTOR.
  
  
 1) COMPLIED.
  
 2) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2ND REQUEST. THE DESIGNER OF RECORD HAS NOT REVIEWED
 THE ENGINEERS WIND DESIGN CRITERIA AND PRESSURES FOR
 THIS PROJECT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 WITH THE NEW WINDOWS AND SLIDDING GLASS DOORS THE PLANS
 DO NOT PROVIDE THE WIND DESIGN CRITERIA;
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4) 2ND REQUEST. PLEASE NOTE THAT PROFLEX 90 DOES NOT
 HAVE ANY TESTING THAT MEETS THE CURRENT CODE FOR SOUND
 UNDER THE (2) SOUND REQUIREMENTS ASTM E-90 AND ASTM
 E-492. THEY DO PASS THE FLAME SPREAD REQUIREMENTS OF
 ASTM-E-84.
  
 THE SUBMITTED REPORT FOR PROFLEX MSC 90 ASTM E-492/ 90
 PAGE 3 OF 4 INDICATES A IIC RATING OF 68 . PAGE (2) OF
 THE REPORT IT DESCRIBES THE FLOOR AS A 8" SLAB, AN
 ENGINEER WOULD HAVE TO VERIFY SLAB THICKNESS. THE OTHER
 ISSUE WITH THIS REPORT IS THE REST WAS CONDUCTED WITH A
 SUSPENDED CEILING , 5/8 TYPE X GYPSUM BOARD AND A 10
 INCH PLENUM WITH 3 1/2 INCHES OF FIBERGLASS INSULATION.
 TEST REPORTS ARE TO BE TESTED WITH NO DROP CEILING
 SINCE THERE IS NO CONTINUAL DROP CEILING OVER THE WHOLE
 CEILING.
  
 THE SAME ISSUE ARE WITH THE PROFLEX MSC 90 REPORT
 TESTED UNDER ASTM E-90, PAGES 3 OF 4 LIST A STC RATING
 OF STC= 72. THE REPORT IT DESCRIBES THE FLOOR AS A 8"
 SLAB, AN ENGINEER WOULD HAVE TO VERIFY SLAB THICKNESS.
 THE OTHER ISSUE WITH THIS REPORT IS THE REST WAS
 CONDUCTED WITH A SUSPENDED CEILING , 5/8 TYPE X GYPSUM
 BOARD AND A 10 INCH PLENUM WITH 3 1/2 INCHES OF
 FIBERGLASS INSULATION. TEST REPORTS ARE TO BE TESTED
 WITH NO DROP CEILING SINCE THERE IS NO CONTINUAL DROP
 CEILING OVER THE WHOLE CEILING.
  
 COMMENTS FROM THE 1ST REVIEW ON THIS CODE ISSUE:
 SUBMITTED IN WITH THE PLANS IS DOCUMENTS FOR FLOOR
 INSULATION PROFLEX 90 FLOOR INSULATION, PLEASE NOTE
 THERE WERE A FEW PERMITS ISSUED WITH THIS PRODUCT BUT
 IT HAS BEEN BROUGHT TO OUR ATTENTION THIS REPORT WITH A
 INSULATION CLASS OF IIC 72 IS WITH A DROPPED CEILING.
 THE PRODUCT IS TO BE TESTED WITH FLOOR TILE, THIN-SET,
 INSULATION MATERIAL AND 6 INCH THICK CONCRETE SLAB. SEE
 THE FOLLOWING CODE REQUIREMENTS, THE FULL TEST
 DOCUMENTS REQUIRED.
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]