2015-04-08 09:25:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030908
 ADD: 6300 GARDEN AVE.
 CONT: GULF ATLANTIC ROOFING
 TEL: ( 561)714-5191
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: WED. APRIL 08/ 2015
 ACTION: DENIED
  
 1A) NOA JOHN MANVILLE INSULATION NOA 14-1015.08 THE
 CONTRACTOR HAS NOT CIRCLED (IDENTIFIED) WHICH
 INSULATION WILL BE APPLIED TO THE 2ND STORY ROOFING
 PERMIT.
  
 1B) GAF RUBEROID MODIFIED BITUMEN ROOF SYSTEMS OVER
 WOOD DECK NOA 14-0611.01 THE CONTRACTOR OF RECORD HAS
 INDICATED ON THE FRONT SHEET OF THIS NOA SYSTEM SYSTEM
 TYPE A(1) PAGE 8. THIS SUB-SYSTEM STARTS ON PAGE 7
 CONTINUES TO PAGE 8, PLEASE CIRCLE WHICH SUB-SYSTEM IS
 TO BE INSTALLED. NOTE LIMITATION # 7 WITH ENHANCED
 FASTENING REQUIREMENTS BY ENGINEER.
  
 1C) THE ENGINEERING LETTER SUBMITTED IS GENERIC, NOT
 SITE SPECIFIC TO LOCATION OF WORK, DOES NOT REFERENCE
 THE PRODUCT APPROVAL NUMBER. NOR THE SUB-SYSTEM, THE
 MAXIMUM DESIGN PRESSURES FOR THE SUB-SYSTEM NOR THE
 LIMITATION 7 OR 9. THE ENGINEER FAILS TO PROVIDE THE
 FASTENER TYPE AS PER SUB-SYSTEM AND THE AMOUNT OF
 REQUIRED ROWS FOR THE WIDTH OF THE PRODUCT. DEPENDING
 ON THE SUB-SYSTEMS THEY PROVIDE THE AMOUNT OF ROWS OR
 THE SPACING BETWEEN ROWS.
  
 CALLED AND SPOKE WITH P. E. ALBERT KWAN
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  