Date |
Text |
2015-03-30 12:19:33 | 3/30/2015 |
| PROJECT: IBIS CLUBHOUSE SITE AND LANDSCAPE LIGHTING |
| PERMIT#: 15030800 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| ASTRONOMICAL TIME SWITCH. INDICATE COMPLIANCE WITH THE |
| FLORIDA ENERGY CODE, 505.2 ON THE PLANS. |
| |
| 2) 2010 FBC-BUILDING SECTION 1609 |
| PROVIDE WIND LOAD CALCULATIONSIN COMPLIANCE WITH THE |
| FBC 1609, (PRIOR TO RELEASE OF PERMIT), FOR ALL LIGHT |
| POLE LIGHTS. INCLUDE THE INSTALLATION OF THE LUMINAIRE |
| ON THE POLE IN THE CALCULATION. |
| |
| 3) PROVIDE PANEL SCHEDULES, AND LOAD CALCULATIONS AS |
| WELL AS THE METHODS AND MATERIALS PROPOSED FOR THE |
| INSTALLATION OF NEW CIRCUITRY. |
| |
| 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, |
| 668.001-668.006 FBC, WPB AMENDMENTS 107.2.. THE PLANS |
| HAVE NOT BEEN SIGNED BY THE ENGINEER. PROVIDE TWO SETS |
| OF SIGNED, SEALED PLANS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |