2015-12-02 13:11:461ST REVIEW 2010 MECHANICAL
 PERMIT #15030795
 12/2/15
  
 1 ) COMMENT #2 FROM THE 1ST REVIEW WILL STAND BASED ON
 THE REVISED DRAWING INDICATING THE ADDITION OF AN
 ENCLOSED PARKING GARAGE ATTACHED TO THE CARPENTRY
 BUILDING. PLEASE REFER TO SECTION 406.3, 406.3.3.1, AND
 406.4.2 FBC-10 BUILDING. SECTION 406.3.3.1: "FOR
 NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF THE
 STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS ON
 TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS." PER THE CODE SECTIONS LISTED
 ABOVE, THE BUILDING IS DEFINED AS AN "ENCLOSED GARAGE".
 I HAVE REPRINTED COMMENT #2 FROM THE 1ST REVIEW BELOW.
 2) IN REFERENCE TO NEW PARKING GARAGES PLEASE REVIEW
 SECTION 404.1 FBC-10 MECHANICAL, AND PROVIDE CONTINUOUS
 MECHANICAL VENTILATION OR A VENTILATION SYSTEM DESIGNED
 TO OPERATE AUTOMATICALLY UPON DETECTION OF A
 CONCENTRATION OF CARBON MONOXIDE OF 25 PARTS PER
 MILLION (25 PPM) BY APPROVED AUTOMATIC DETECTION
 DEVICES (CO DETECTORS). PLEASE NOTE THAT AUTO OPERATION
 OF THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW
 RATE BELOW 0.05 CFM PER SQ. FT. OF THE FLOOR AREA AND
 THE SYSTEM SHALL BE CAPABLE OF PRODUCING A VENTILATION
 AIRFLOW OF 0.75 CFM PER SQ. FT. OF FLOOR AREA.
  