Plan Review Notes
Plan Review Notes For Permit 15030795
Permit Number 15030795
Review Stop E
Sequence Number 3
Notes
Date Text
2016-01-29 10:17:42ISSUED WITH ELECTRICAL PROVISO:
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22
 PROVIDE HIGH LEG IDENTIFICATION AT THE ELECTRICAL
 SERVICE AND PANEL BOARDS. NEC 408.3, 110.15, 230.56
 SERVICE NEUTRAL REQUIRED FOR 3 PHASE SERVICE. NEC
 250.24(C)
 PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES
 IN GARAGE. NEC 210.8
 PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL
 SERVICE. NEC 250 .94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  