2015-12-16 15:06:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030795
 ADD: 5390 GEORGIA AVE.
 CONT: TIM GIVENS BUILDING
 TEL: (561)533-5825
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. DEC. 16I/2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4A)(1) SEMI- COMPLIED. THE PLANS DO NOT PROVIDE
 OCCUPANCY SEPARATION WALLS. PLEASE IDENTIFY THE
 OCCUPANCY SEPARATION WALLS BETWEEN THE F1 & S1
 OCCUPANCIES AND HOUR RATING OF WALL AND OPENING
 PROTECTIVE.
 2010 FBC-B TABLE 508.4
 2010 FBC-B TABLE 715.4.
  
 4A)(2) COMPLIED. 1 ? HR. OPENING PROTECTION. DOOR # 4
 IS SHOWN TO BE IN A 2 HOUR FIRE RATED WALL, THE DOOR
 SCHEDULE INDICATES THIS DOOR IS TO HAVE GLAZING IN THE
 DOOR, PLEASE PROVIDE THE AMOUNT OF SQ. INCHES IN THIS
 DOOR. 2010 FBC-B TABLE 715.5.4.
  
 4B)NEW ISSUE: THE CARPENTRY WORK SHOP (F1 OCCUPANCY)
 AND S1 THE WOOD STORAGE DID NOT REQUIRE A FIRE BARRIER
 ( TABLE 508.4). THE NEW SET OF PLANS NOW SHOWS A CAR
 PARKED WITHIN THE SPACE PREVIOUSLY SHOWN AS A F1/ S1
 OCCUPANCY. CAR STORAGE IN A RESIDENCE IS A U OCCUPANCY
 BUT IN A COMMERCIAL APPLICATION SECTION 2010 FBC-B
 311.3 PUTS OPEN AND ENCLOSED GARAGES AS A S-2 LOW
 HAZARD. TABLE 508.4 WILL REQUIRE A 2 HR. WALL BETWEEN
 THE S2 ENCLOSED GARAGE AND THE F1 & S1 OCCUPANCIES.
  
 4C) 2010 FBC-B 406.4.2 VENTILATION. A MECHANICAL
 VENTILATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL.
  
 5-11) COMPLIED.
  
 12) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) NOTICE ONLY! THIS PROJECT HAS REQUESTED PRIVATE
 PROVIDER TEW & TAYLOR FOR ONSITE INSPECTIONS. FORMS
 HAVE BEEN SUBMITTED AND FILED OUT.
  
 13A)NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 14) COMPLIED. IMPACT FEES PAID TO PALM BEACH COUNTY.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  