2015-12-16 15:06:55 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15030795 |
| ADD: 5390 GEORGIA AVE. |
| CONT: TIM GIVENS BUILDING |
| TEL: (561)533-5825 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: WED. DEC. 16I/2015 |
| ACTION: DENIED |
| |
| 1-3) COMPLIED. |
| |
| 4A)(1) SEMI- COMPLIED. THE PLANS DO NOT PROVIDE |
| OCCUPANCY SEPARATION WALLS. PLEASE IDENTIFY THE |
| OCCUPANCY SEPARATION WALLS BETWEEN THE F1 & S1 |
| OCCUPANCIES AND HOUR RATING OF WALL AND OPENING |
| PROTECTIVE. |
| 2010 FBC-B TABLE 508.4 |
| 2010 FBC-B TABLE 715.4. |
| |
| 4A)(2) COMPLIED. 1 ? HR. OPENING PROTECTION. DOOR # 4 |
| IS SHOWN TO BE IN A 2 HOUR FIRE RATED WALL, THE DOOR |
| SCHEDULE INDICATES THIS DOOR IS TO HAVE GLAZING IN THE |
| DOOR, PLEASE PROVIDE THE AMOUNT OF SQ. INCHES IN THIS |
| DOOR. 2010 FBC-B TABLE 715.5.4. |
| |
| 4B)NEW ISSUE: THE CARPENTRY WORK SHOP (F1 OCCUPANCY) |
| AND S1 THE WOOD STORAGE DID NOT REQUIRE A FIRE BARRIER |
| ( TABLE 508.4). THE NEW SET OF PLANS NOW SHOWS A CAR |
| PARKED WITHIN THE SPACE PREVIOUSLY SHOWN AS A F1/ S1 |
| OCCUPANCY. CAR STORAGE IN A RESIDENCE IS A U OCCUPANCY |
| BUT IN A COMMERCIAL APPLICATION SECTION 2010 FBC-B |
| 311.3 PUTS OPEN AND ENCLOSED GARAGES AS A S-2 LOW |
| HAZARD. TABLE 508.4 WILL REQUIRE A 2 HR. WALL BETWEEN |
| THE S2 ENCLOSED GARAGE AND THE F1 & S1 OCCUPANCIES. |
| |
| 4C) 2010 FBC-B 406.4.2 VENTILATION. A MECHANICAL |
| VENTILATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH |
| THE FLORIDA BUILDING CODE, MECHANICAL. |
| |
| 5-11) COMPLIED. |
| |
| 12) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 13) NOTICE ONLY! THIS PROJECT HAS REQUESTED PRIVATE |
| PROVIDER TEW & TAYLOR FOR ONSITE INSPECTIONS. FORMS |
| HAVE BEEN SUBMITTED AND FILED OUT. |
| |
| 13A)NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM |
| BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| JOBSITE INSPECTIONS. |
| |
| 14) COMPLIED. IMPACT FEES PAID TO PALM BEACH COUNTY. |
| JAMES A. WITMER CBO |