Plan Review Notes
Plan Review Notes For Permit 15030795
Permit Number 15030795
Review Stop P
Sequence Number 2
Notes
Date Text
2015-09-04 17:35:492ND REVIEW: FBC 2010
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.WIDTH OF NEW BATHROOM DOES NOT ALLOW CLEARANCE AROUND
 TOILET MUST .
 FBC ACC. 2010 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 2.SHOW HEIGHT OF WET BAR SHALL COMPLY WITH. FBC ACC.
 2010 804.3.2 HEIGHT.
 THE KITCHEN WORK SURFACE SHALL BE 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 3.SHEET C1 IS STILL SHOWING 2 WET BARS.
 4. MINIMUM NUMBER OF PLUMBING FIXTURES FBCP 403.
 TABLE 403.1 FOR F1 OCCUPANCY REQUIRES 1 DRINKING
 FOUNTAIN AND 1 SERVICE SINK.