Plan Review Notes
Plan Review Notes For Permit 15030795
Permit Number 15030795
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-12 04:46:461) SHT. A-000 - BUILDING SUMMARY - NOTES THIS AS A
 LEVEL 1 ALTERATION. HOW CAN THIS BE CLASSIFIED AS A
 LEVEL 1 ALTERATION WHEN IT IS AN ADDITION AND NEW
 CONSTRUCTION? CLARIFY.
 2) SHT. A-000 - BUILDING SUMMARY - THE OCCUPANCY IS
 LISTED AS "I" - INDUSTRIAL. GROUP I OCCUPANCY IS
 INSTITUTIONAL IN CHAPTER 3 OF THE FBC. THIS WOULD BE
 CONSIDERED A GROUP F OCCUPANCY. PLEASE REFER TO CHAPTER
 3 OF THE 2010 FBC FOR THE CORRECT TYPE OF F OCCUPANCY
 AND NOTE THE CORRECT TYPE OF OCCUPANCY ON SHT. A-000.
 3) SHT. A-100 - THE WET BAR SHALL COMPLY WITH THE 2010
 FL. ACCESSIBILITY CODE SEC.212.3 & 606.
 4) THE TOILET ROOM IS NOT WIDE ENOUGH TO PROVIDE THE
 SPACE NEEDED FOR THE PLUMBING FIXTURES PER THE FLORIDA
 ACCESSIBILITY CODE SECS. 604.3,604.3.2, FBC-PLUMBING,
 SEC.404.3.1.
 5) SHTS. C-1, LP-1 SHOWS TWO WET BARS ( ONE ADJACENT TO
 THE NEW TOILET ROOM) AND THE ARCHITECTURAL AND PLUMBING
 SHEET ONLY SHOWS ONE. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  