2015-03-26 12:24:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | A LIFE SAFETY PLAN SHALL BE SUBMITTED THAT INCLUDES, | | OCCUPANCY LOADS, EQUIPMENT PLAN, EGRESS PATHS OF | | TRAVEL, COMMON PATHS OF TRAVEL, EXITS THAT LEAD TO A | | PUBLIC WAY, EXIT SIGNS, EMERGENCY LIGHTS, FIRE | | EXTINGUISHER LOCATIONS, | | | | PER NFPA 1, 13.3.2.28 WOODWORKING OPERATIONS. AN | | APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM SHALL BE | | INSTALLED IN BUILDINGS CONTAINING WOODWORKING | | OPERATIONS EXCEEDING 2500 FT2 THAT USE EQUIPMENT, | | MACHINERY, OR APPLIANCES, THAT GENERATE FINELY DIVIDED | | COMBUSTIBLE WASTE, OR THAT USE FINELY DIVIDED | | COMBUSTIBLE MATERIALS. | | | | THE FIRE SPRINKLER SYSTEM SHALL BE MONITORED. | | | | PROVIDE OCCUPANY FIRE RATING SEPARATIONS INCLUDING | | RATED DOORS FROM OFFICE, CARPENTRY SHOP, STORAGE, | | MERCANTILE AREAS, MINIMUM 1 HOUR WITH FIRE SPRINKLER | | SYSTEM. |
|