2015-04-10 16:15:55 | 4/10/2015 | | PROJECT: 5390 GEORGIA AVE ADDITION AND SITE WORK | | PERMIT#: 15030795 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) REVISE THE RISER DIAGRAM TO ADDRESS THE FOLLOWING: | | A) THE 3PHASE ELECTRICAL FEEDERS TO REFLECT THE CORRECT | | NUMBER OF CONDUCTORS FOR A 3PHASE FEEDER. | | B) PROVIDE THE NUMBER, SIZE, AND TYPE OF WIRES IN THE | | SERVICE ENTRANCE RISER CONDUITS. | | | | 2) INDICATE COMPLIANCE WITH FBC-E 505.2 FOR INTERIOR | | AND EXTERIOR LIGHTING CONTROL. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|