Plan Review Notes
Plan Review Notes For Permit 15030795
Permit Number 15030795
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-10 16:15:554/10/2015
 PROJECT: 5390 GEORGIA AVE ADDITION AND SITE WORK
 PERMIT#: 15030795
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO ADDRESS THE FOLLOWING:
 A) THE 3PHASE ELECTRICAL FEEDERS TO REFLECT THE CORRECT
 NUMBER OF CONDUCTORS FOR A 3PHASE FEEDER.
 B) PROVIDE THE NUMBER, SIZE, AND TYPE OF WIRES IN THE
 SERVICE ENTRANCE RISER CONDUITS.
  
 2) INDICATE COMPLIANCE WITH FBC-E 505.2 FOR INTERIOR
 AND EXTERIOR LIGHTING CONTROL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  