Plan Review Notes For Permit 15030785 |
Permit Number |
15030785 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-08 17:16:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | [email protected] | | | | FBC FLORIDA BUILDING CODE 2010 | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED - | | ONLY ONE SET WAS PROVIDED | | TWO SETS REQUIRED FOR PERMIT ISSUANCE | | | | 1. PROVIDE A SECOND COPY OF THE STC TEST, FBC 107. | | | | 2. PROVIDE A SECOND COPY OF THE IIC TEST, FBC 107. | | ALTHOUGH THE RESULT IS 49, THE TEST IS FOR A 6" SLAB, | | THIS BUILDING HAS A 7" PT SLAB. | | | | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | E 84 OR UL 723. | | | | 2ND REVIEW, NOT PROVIDED. PROVIDE TWO SETS. | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. | | | | 2ND REVIEW, NOT PROVIDED. | | | | | | |
|