Plan Review Notes For Permit 15030748 |
Permit Number |
15030748 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-05 14:12:42 | 15030748 | | 1590 CAMERON SAMUEL LANE | | LAKE FOUNTAINS | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS | | | | PROVIDE AN ELECTRICAL RISER PLAN FOR EACH FOUNTAIN. NEC | | 215.5 | | | | PROVIDE THE LOCATION OF EACH DISCONNECTING MEANS. NEC | | 682.14 | | | | PROVIDE A SITE PLAN WHICH SHOWS THE LOCATION OF ALL | | ELECTICAL EQUIPMENT AND UNDERGROUND WIRING. NEC 682.11 | | | | INDICATE THE LOCATION OF THE ELECTRICAL DATUM PLANE ON | | THE SITE PLAN FOR EACH INSTALLATION. NEC 682.10 | | | | PROVIDE A CONSTRUCTION DETAIL AND LOCATION FOR EACH | | EQUIPOTENTIAL PLANE REQUIRED FOR THE SERVICE, | | DISCONNECTS AND CONTROL EQUIPMENT. NEC 682.33 | | | | NOTE: SEPARATE PERMITS WITH A SEPARATE ADDRESS IS | | REQUIRED FOR EACH FOUNTAIN. PROVIDE THREE SEPARATE | | PERMITS FROM AN ELECTRICAL CONTRACTOR FOR THIS | | INSTALLATION. PROVIDE A COPY OF THE CONTRACT FOR THE | | COMPLETE INSTALLATION, MATERIALS AND LABOR. | | | | ROBERT LECKY | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | |
|