Plan Review Notes For Permit 15030744 |
Permit Number |
15030744 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-07-06 11:06:28 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52 | | | | 2) WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) | | OF THE OUTSIDE EDGE OF THE SINK GROUND-FAULT | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IS | | REQUIRED. NEC 210.8 (B) (5) SINKS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|