Plan Review Notes
Plan Review Notes For Permit 15030744
Permit Number 15030744
Review Stop P
Sequence Number 2
Notes
Date Text
2015-05-27 03:30:151)THE PERMIT APPLICATION AND PLANS ARE VAGUE AS TO THE
 EXTENT OF PLUMBING WORK THAT WILL BE DONE IN THIS
 SPACE.SUBMIT INFORMATION AND ON THE PLANS SHOWING THE
 ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.107.1.2.
 SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR
 REVIEW. ONE SET OF PLANS IS SO LIGHT THEY ARE
 ILLEGIBLE.PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE
 AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1
 2) IS ANY EQUIPMENT/ PEDICURE CHAIRS THAT USE WATER
 BEING INSTALLED? IF SO, SUBMIT MANUFACTURER'S
 SPECIFICATIONS & INSTALLATION INSTRUCTIONS FOR THE
 EQUIPMENT.IDENTIFY THE CHAIRS ON THE PLAN IF
 APPLICABLE. NOW THERE IS JUST IMAGES NOTED AS "SEAT
 WITH STOOL".
 3) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC.107.3.5.1.3.
 4) BOTH SETS OF PLANS SHALL BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 RULE 61G1-16.003.
 5)SHT. A-1 - HANDICAP DETAILS - THE GRAB BAR SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOW. FAC
 SEC. 609.4.
 6) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. SHOW THIS ON THE HANDICAP
 DETAILS.
 7) THE FINISH SCHEDULE ON SHT A-1 NOTES THE TOILET ROOM
 WALLS TO BE PAINTED AND A 2 INCH WOOD BASE
 INSTALLED.THE BASE SHALL BE A MINIMUM OF 4 INCHES AND
 COMPLY WITH FBC SEC.1210.1. THE WALLS & PARTITIONS
 WITHIN 2 FEET OF WATER CLOSETS SHALL HAVE SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR AND COMPLY WITH FBC SEC. 1210.2.
 8) INDICATE ON THE PLANS WHAT PLUMBING IS NEW AND WHAT
 IS EXISTING TO REMAIN. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHT. E-1 SHOWS A 100 GALLON WATER HEATER. IS THIS
 CORRECT?
 10) SHT. E-1 - SUBMIT A WATER RISER DIAGRAM FOR REVIEW.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE PLAN VIEW
 REQUIRES A MAGNIFYING GLASS TO REVIEW. PLANS SHALL BE
 DRAWN ON A MIN. OF 1/8 " SCALE AND SHALL CLEARLY SHOW
 THE SCOPE OF WORK TO BE DONE. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  