Plan Review Notes For Permit 15030744 |
Permit Number |
15030744 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-17 05:43:11 | 1)THE PERMIT APPLICATION AND PLANS ARE VAGUE AS TO THE | | EXTENT OF PLUMBING WORK THAT WILL BE DONE IN THIS | | SPACE.SUBMIT INFORMATION AND ON THE PLANS SHOWING THE | | ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.107.1.2. | | SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR | | REVIEW. PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE | | AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE. | | WPB AMEND. TO 2010 FBC SEC. 107.2.1 | | 2) IS ANY EQUIPMENT/CHAIRS THAT USE WATER BEING | | INSTALLED? IF SO, SUBMIT MANUFACTURER'S SPECIFICATIONS | | & INSTALLATION INSTRUCTIONS FOR THE EQUIPMENT. | | 3) IF ANY CHANGES ARE BEING DONE TO THE PLUMBING | | SYSTEM, SUBMIT A SANITARY AND WATER RISER FOR REVIEW. | | WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3. | | 4) A DRINKING FOUNTAIN WILL BE REQUIRED IN THIS BAY. | | THE 2010 FL. ACCESSIBILITY CODE REQUIRES A MINIMUM OF | | TWO DRINKING FOUNTAINS PER SEC. 211.2. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | 2015-03-23 17:36:24 | SEE PERMIT APPLICATION. JG. |
|