2015-04-07 15:19:14NO ELECTRICAL PLANS HAVE BEEN INCLUDED IN THIS
 SUBMITTAL PACKAGE. AN APPLICATION WITH THE DESCRIPTION
 MINOR INTERIOR REMODEL INCLUDING ELECTRIC AND PLUMBING
 FOR NEW FOOT MASSAGE BUSINESS. PROVIDE COMPLETE
 ELECTRICAL PLANS REQUIRED TO INDICATE COMPLIANCE WITH
 THE FBC AND THE NEC
 PROVIDE A FLOOR PLAN INDICATING LOCATIONS FOR THE
 ELECTRICAL SERVICE, ELECTRICAL PANEL(S) FOOT MASSAGE
 EQUIPMENT. LWPB AMENDMENTS TO FBC 107.3.2, NEC 110.26
 PROVIDE A PANEL SCHEDULE INDICATING ALL NEW CIRCUITS
 FOR NEW FOOT MASSAGE EQUIPMENT. NEC 408.4
 PROVIDE A LOAD CALCULATION THAT INCLUDES ALL EXISTING
 PLUS ADDITIONAL BRANCH CIRCUITS REQUIRED FOR NEW FOOT
 MASSAGE EQUIPMENT.
2015-03-23 17:35:56SEE PERMIT APPLICATION. JG.