Plan Review Notes For Permit 15030741 |
Permit Number |
15030741 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-23 07:16:21 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO COPIES OF THE SPECIFICATIONS FOR THE POOL | | HEATING EQUIPMENT WITH THE ELECTRICAL REQUIREMENTS. FBC | | 107.2.1.3 | | | | 2) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS TO | | SHOW THAT THE EXISTING ELECTRICAL SYSTEM CAN HANDLE THE | | ADDITIONAL LOADS. NEC 220.40 | | |
|