Plan Review Notes For Permit 15030731 |
Permit Number |
15030731 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-02 07:04:14 | 333 FERN STREET | | PERMIT #15030731 | | REVIEW COMMENTS - FIRE DEPARTMENT | | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY | | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE | | (2012 EDITION WITH FLORIDA AMENDMENTS.) | | | | RESPONSE COMMENT - SINCE THIS BACKFLOW PREVENTER IS | | LOCATED ON PRIVATE PROPERTY WPB UTILITIES DOES NOT HAVE | | JURISDICTION. PER FLORIDA STATUTE 633 THE FIRE MARSHAL | | IS RESPONSIBLE FOR ENFORCEMENT OF THE FIRE CODE; | | THEREFORE, COMPLIANCE WITH THE COMMENT BELOW IS | | REQUIRED. | | ORIGINAL COMMENT - SHEET C-09: PER NFPA 24 SECTION | | 6.2.1, BACKFLOW PREVENTER CONTROL VALVES SHALL BE | | INSTALLED IN A FIRE-RATED ROOM ACCESSIBLE FROM THE | | EXTERIOR. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|