Plan Review Notes
Plan Review Notes For Permit 15030731
Permit Number 15030731
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-04-02 07:04:14333 FERN STREET
 PERMIT #15030731
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 RESPONSE COMMENT - SINCE THIS BACKFLOW PREVENTER IS
 LOCATED ON PRIVATE PROPERTY WPB UTILITIES DOES NOT HAVE
 JURISDICTION. PER FLORIDA STATUTE 633 THE FIRE MARSHAL
 IS RESPONSIBLE FOR ENFORCEMENT OF THE FIRE CODE;
 THEREFORE, COMPLIANCE WITH THE COMMENT BELOW IS
 REQUIRED.
 ORIGINAL COMMENT - SHEET C-09: PER NFPA 24 SECTION
 6.2.1, BACKFLOW PREVENTER CONTROL VALVES SHALL BE
 INSTALLED IN A FIRE-RATED ROOM ACCESSIBLE FROM THE
 EXTERIOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730