Plan Review Notes For Permit 15030727 |
Permit Number |
15030727 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-18 14:21:35 | IN CONVERSATION WITH THE CONTRACTOR IT WAS DECIDED THAT | | THE NEW OUTLET SHOWN ON THE PLANS IS NOT NECESSARY AND | | THUS REMOVED FROM THE PERMIT. FURTHERMORE, I.WAS | | INFORMED THAT THE REQUIRED LIGHT OUTSIDE THE FOYER | | DOOR, AND THE SMOKE DETECTORS ARE ALREADY EXISTING; NOT | | INCLUDED ON THE PLANS. THEREFORE NO ELECTRICAL PERMIT | | IS REQUIRED AND THE HOLD WILL BE LIFTED. | 2015-05-29 12:51:25 | IMPORTANT NOTICE TO CONTRACTOR: | | 1. A SEPARATE ELECTRICAL PERMIT SHALL BE SECURED FOR | | THIS WORK | | 2. NEC 210.70 REQUIRES A LIGHT WITH A SWITCH ON THE | | EXTERIOR SIDE OF THE DOOR. | | 3. YOU SHALL COMPLY W/FBC-R314.3.1 AND INSTALL THE | | REQUIRED SMOKE DETECTORS. | | IT IS NOT THE INTENT OF THIS NOTE TO MAKE YOU GO BEYOND | | THE SCOPE OF YOUR WORK, BUT IF YOU ARE GOING TO BE | | WORKING AT THE FRONT DOOR AND PUTTING THE LIGHT, IF NOT | | ALREADY THERE IS NOT TOO MUCH OF A PROBLEM, THIS PERMIT | | WILL ALLOW YOU TO DO SO. | | |
|