2015-03-23 13:59:17 | 1) THE RELIEF VALVE DISCHARGE FROM THE WATER HEATER |
| SHALL DISCHARGE THROUGH AN AIR GAPLOCATED IN THE SAME |
| ROOM AS THE WATER HEATER PER THE 2010 FPC SEC.504.6 |
| (2). |
| 2) THE DRAWING SHOWS AN 1 1/2" FORCE MAIN DISCHARGING |
| INTO A STACK. INDICATE ON THE DRAWINGS IF THIS IS A NEW |
| OR AN EXISTING LINE.IF IT IS SUBMIT COMPLETE RISER |
| DIAGRAM FOR THE PIPING, MANUF. SPEC SHEETS FOR THE SUMP |
| BASIN AND PUMPS, ELECTRICAL PLANS, ETC. THE |
| INSTALLATION SHALL COMPLY WITH THE 2010 FPC SEC.712. |
| 3) THE PLAN NOTES "INSTALL ON OUTSIDE OF BUILDING |
| WALL." CLARIFY WHERE THIS PIPE IS BEING INSTALLED. IS |
| IT BEING INSTALLED ON AN EXTERIOR WALL OF THE BUILDING? |
| IF SO, ANY PVC PIPING MUST BE PROTECTED FROM UV RAYS |
| PER THE MANUFACTURER'S RECOMMENDATIONS AND ASTM |
| STANDARD. INDICATE HOW THIS WILL BE DONE. |
| 4) CLEANOUTS ARE REQUIRED IN ALL STACKS PER THE 2010 |
| FBC SEC.708.3.4. |
| 5) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE |
| SINKS.SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR |
| REVIEW. PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE |
| AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE. |
| WPB AMEND. TO 2010 FBC SEC. 107.2.1 |
| 6) THE PLANS NOTE THE SINKS AS KITCHEN SINKS. WILL |
| THESE SINKS BE USED IN THE PREPARATION OF FOOD? IF SO, |
| APPROVAL FROM THE DEPT. OF BUSINESS & REGULATION, |
| DIVISION OF HOTELS AND RESTAURANTS IS REQUIRED. |
| INDICATE ON THE PLANS EXACTLY WHAT THESE SINKS WILL BE |
| USED FOR. |
| 7) IF THE SINKS WILL BE USED IN THE PREPARATION OF FOOD |
| THEY SHALL BE INDIRECTLY WASTED TO THE PLUMBING SYSTEM |
| PER THE 2010 FPC SEC.802. CLARIFY. |
| 8) THE EXISTING DRAWINGS THAT WERE SUBMITTED WITH THESE |
| PLANS ARE ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE DRAWINGS |
| FOR REVIEW. |
| 9) IF THE SINKS ARE USED FOR FOOD PREPARATION THEY |
| SHALL DISCHARGE THROUGH A GREASE INTERCEPTOR. CLEARLY |
| INDICATE THE USE OF THESE SINKS ON THE PLANS. 2010 FPC |
| SEC.1003.1. SUBMIT INFO ON THE EXISTING GREASE TRAP |
| (SIZE) AND SUBMIT CALCULATIONS FOR THESE SINKS. 2010 |
| FPC SEC.1003.2, 1003.3.4. |
| 10) IF THE SINKS ARE NOT BEING USED FOR FOOD |
| PREPARATION, THEY WILL BE REQUIRED TO MEET HANDICAP |
| ACCESSIBILITY HEIGHT REQUIREMENTS. FL. AACCESSIBILITY |
| CODE SEC.212.2, 804, 606. SHOW COMPLIANCE ON THE |
| ELEVATION DRAWINGS FROM LOWE'S. |
| 11) SHOW THE DISHWASHER ON THE SANITARY RISER DIAGRAM |
| AND HOW IT WILL DRAIN TO THE SANITARY SYSTEM. IF THIS |
| IS A NEW INSTALLATION THEN ELECTRICAL PLANS WILL BE |
| REQUIRED FOR THE DISHWASHER AND THE WATER HEATER IF THE |
| WATER HEATER IS ELECTRIC. THE DISHWASHER SHALL |
| DISCHARGE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| STANDPIPE OR WASTE RECEPTOR PER THE 2010 FBC SEC. |
| 802.1.7. |
| 12 ) INDICATE CAPACITY ( GALLONS) OF THE WATER HEATER. |
| IINDICATE IF THE WATER HEATER IS REPLACIBNG AN EXISTING |
| ONE OR IS BEING ADDED. |
| 13) INDICATE ON THE PLAN IF THE WATER HEATER IS |
| ELECTRIC OR GAS. IF GAS, SUBMIT COMPLETE GAS PLANS AND |
| SPEC. SHEETS FOR THE WATER HEATER. |
| |
| THE SUBMITTED PLANS DO NOT CLEARLY REFLECT THE USE OF |
| THESE SINKS. I SUGGEST CALLING ME TO SET UP A MEETING |
| TO DISCUSS THIS PLAN REVIEW. |
| |