Plan Review Notes
Plan Review Notes For Permit 15030660
Permit Number 15030660
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-12 11:39:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEE FBC 107.3.5 FOR MINIMUM PLAN REVIEW CRITERIA.
 PLANS ARE TO BE ARCHITECTURAL QUALITY, TO SCALE,
 CLEARLY SHOWING SCOPE OF WORK AND LOCATION OF ALL
 IMPROVEMENTS INCLUDING WINDOW SIZES.
  
 2ND REVIEW; GOOD QUALITY PLANS PREPARED BY AN ARCHITECT
 WERE SUBMITTED. SEE BELOW FOR NEW COMMENTS ON THE NEW
 PLAN PROVIDED (1ST REVIEW FOR ARCHITECT'S PLAN).
  
 2. PROVIDE STRUCTURAL DETAILS FOR FRAMING AND STUCCO.
 FBC 107
  
 2ND REVIEW; SEE NEW COMMENTS BELOW.
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 COMPONENTS AND CLADDING, FAC9N-3.
  
 2ND REVIEW; NOT ADDRESSED. PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC
 107.
  
 NEW COMMENTS (FIRST REVIEW FOR PLAN DATED 7/8/15
 PREPARED BY ERIC TREBBIEN, TREB ARC, INC):
  
 4. SEE FS481, A BUSINESS LICENSE FROM THE FLORIDA BOARD
 OF ARCHITECTS IS REQUIRED TO PRACTICE ARCHITECTURE
 THROUGH A COMPANY (TREB ARC, INC) AND THAT BUSINESS
 NUMBER IS TO BE INCLUDED IN THE TITLE BLOCK. YOU CAN
 SEE THE STATUTE AND RULE ONLINE:
  
 HTTPS://WWW.FLRULES.ORG/GATEWAY/CHAPTERHOME.ASP?CHAPTER
 =61G1-16
  
 PROVIDE LICENSE NUMBER ON ANY SHEETS WHICH ARE REVISED
 AS A RESULT OF THIS COMMENT LIST. IF THE COMPANY DOES
 NOT HAVE A LICENSE NUMBER, PLEASE APPLY IMMEDIATELY.
 PERMIT WILL BE ISSUED WITH PROVISO (PROVIDE LICENSE
 NUMBER WHEN ISSUED BY FLORIDA BOARD OF ARCHITECTS).
  
 5. THE FIRST APPLICATION FOR THIS PROJECT WAS SUBMITTED
 ON 3/17/15, SO FBC 2010 SHOULD BE GOVERNING CODE. A
 CHANGE OF CONTRACTOR WAS SUBMITTED ON 7/16/15, AND
 PLANS REFER TO FBC 5TH EDITION (FBC 2014). UPON WRITTEN
 REQUEST, APPLICANT (ARCHITECT OR CONTRACTOR) CAN, IN
 WRITING, REQUEST THAT THE FIRST APPLICATION BE REVOKED
 AND THE SECOND APPLICATION SUBMITTED ON 7/16/15 WILL BE
 CONSIDERED THE FIRST APPLICATION SO GOVERNING CODE WILL
 BE FBC 5TH EDITION. THE APPLICATION DATE WILL BE
 CHANGED IN THE SOFTWARE SYSTEM, A NOTE ADDED TO EXPLAIN
 THE PERMIT NUMBER / CODE VERSION DISCREPANCY.
  
 OR, APPLICANT CAN ELECT TO KEEP THE APPLICATION DATE OF
 3/17/15, AND REVISE ALL PLANS TO CORRECT GOVERNING CODE
 (WITH APPLICATION DATE OF 3/17/15 THIS SHOULD BE FBC
 2010).
  
 AS ARCHITECT USED FBC 5TH EDITION FOR DESIGN, ALL
 COMMENTS REFER TO FBC 5TH EDITION.
  
 6. PLANS ARE TO INCLUDE ALL ITEMS INSTALLED WITHOUT
 PERMIT. PLANS STATE THAT EXISTING ELECTRICAL TO REMAIN,
 NEW METER ONLY. I WAS UNABLE TO LOCATE AN ELECTRICAL
 PERMIT FOR THIS PROPERTY, SO ANY ELECTRICAL WORK DONE
 AFTER THE FIRST CONSTRUCTION OF THE STRUCTURES MAY HAVE
 BEEN DONE WITHOUT PERMITS. PLANS STATE THAT NO
 MECHANICAL WORK IS PROPOSED AND SHALL REMAIN, BUT THE
 VIOLATION INCLUDED MECHANICAL AND I WAS NOT ABLE TO
 FIND RECORD OF ANY MECHANICAL PERMITS.
  
 IT IS SUGGESTED THAT A RECORDS RESEARCH REQUEST BE
 SUBMITTED ([email protected], [email protected]) TO
 ASSIST DESIGNER IN DETERMINING WHAT ITEMS SHOULD BE
 INCLUDED IN THE PLAN.
  
 IF THIS PROPERTY IS CONTRIBUTING HISTORIC, AN EMAIL
 FROM THE HISTORIC PRESERVATION PLANNER WILL BE PUT ON
 FILE WITH THIS PERMIT FOR CONFIRMATION (SEE FBC 5TH
 EDITION ENERGY CONSERVATION 101.4.2). IF THE STRUCTURES
 ARE NOT HISTORIC, AND APPLICANT IS UNABLE TO LOCATE A
 PERMIT FOR MECHANICAL INSTALLATION, ENERGY CALCS WILL
 BE REQUIRED, FBC 5TH EDITION EXISTING BUILDING 707,
 ENERGY CONSERVATION 101.5.1.
  
 7. CS1 DESIGN LOAD SCHEDULE, CLARIFY IMPORTANCE FACTOR
 1.21, BUILDING CATEGORY II, NOT CLEAR WHERE 1.21 FACTOR
 WAS USED IN CALCULATIONS AND DESIGN.
  
 8. SEE PREVIOUS LIST, FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR ALL COMPONENTS AND CLADDING,
 FAC9N-3, FBC RESIDENTIAL 301. PRODUCT APPROVALS TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC
 107.
  
 9. SCOPE OF WORK NOT CLEAR. PLANS PROVIDE A SPEC FOR A
 ROOF; WAS ROOFING WORK DONE, OR IS ROOFING WORK
 PROPOSED? IF ROOFING WORK WAS DONE WITHOUT PERMIT,
 INCLUDE THE PRODUCT APPROVAL. A ROOFING PERMIT
 APPLICATION SUBMITTED BY A LICENSED ROOFING CONTRACTOR
 WILL BE REQUIRED. PLAN SHOULD BE REVISED TO SHOW SCOPE
 OF ROOF REPAIR WORK (CANNOT EXCEED 25%).
  
 IF A NEW ROOF HAS NOT BEEN INSTALLED BUT WILL BE
 PROPOSED, IT IS SUGGESTED THAT THE ROOF SPEC BE REMOVED
 FROM THE PLAN AND INDICATE THAT A REROOF WILL BE UNDER
 SEPARATE PERMIT.
  
 10. PLANS STATE THAT REPAIRS WILL BE DONE "AS NEEDED."
 PLANS TO SHOW SCOPE, FBC 107. INDICATE AREAS OF
 PROPOSED REPAIR, APPROXIMATE SCOPE. IT IS NOT CLEAR
 WHETHER THE ENTIRE OUTSIDE OF THE STRUCTURE IS TO BE
 REPAIRED, OR SO MANY AREAS THAT IT IS TOO DIFFICULT TO
 INDICATE ALL AREAS, OR IF REPAIR AREA IS LIMITED TO
 SMALL AREAS.
  
 11. FBC 5TH EDITION EXISTING BUILDING, 702.4, 707.2,
 ALL NEW ELEMENTS TO COMPLY WITH THE FBC. DETAIL 01 A3,
 BOND BREAK REQUIRED FOR STUCCO, FBC 5TH ED RESIDENTIAL
 703.6.3. ONLY ONE LAYER SHOWN, TWO REQUIRED.
  
 12. DETAIL 5 A3 DOES NOT INCLUDE ANY STRUCTURAL
 INFORMATION AT ALL (MATERIALS, DIMENSIONS, FASTENERS,
 ETC). A1 NOTES SPEC "SIMPSON TIES AS SPECIFIED ON
 PLAN." NOTHING IS SPECIFIED ON THE PLAN. OTHER DETAILS
 ARE NOT SPECIFIC AS TO REQUIREMENTS; FOR INSTANCE,
 DETAIL 1 A3 STATES "EXIST SOLE PLATE ANCHORED TO EXIST.
 FOOTING AS REQUIRED." THIS IS A REPAIR DETAIL; IS THIS
 ITEM (SOLE PLATE) EXISTING OR IS THIS BEING REPAIRED?
 REVISE ALL DETAILS TO BE CLEAR AS TO WHAT IS EXISTING
 TO REMAIN, WHAT IS A SPECIFICATION FOR REPAIR, AND
 FASTENING IS TO BE SPECIFIED. THE PHRASE "AS REQUIRED"
 IS NOT CLEAR - AS REQUIRED BY WHO? YOU, CONTRACTOR,
 OWNER, INSPECTOR? IS THE PLATE EXISTING AND ADDITIONAL
 FASTENERS PROPOSED? WHAT FASTENERS? SEE FBC 107; PLANS
 TO SHOW SCOPE AND NATURE OF PROPOSED CONSTRUCTION. THIS
 IS ONE EXAMPLE. REVISE ALL AS APPLICABLE.
  
  
  