2015-09-16 16:40:37PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL PROVIDE A SITE PLAN SHOWING THE LOCATION
 OF THE EXISTING METER AND MAIN DISCONNECT.
 2. YOU SHALL PROVIDE A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM, WITH LOAD CALCS AND WIRING SCHEDULES. INCLUDE
 THE REQUIRED GROUNDING AND INTER-SYSTEM BONDING
 TERMINAL.
 3. REPLACEMENT RECEPTACLES SHALL COMPLY WITH NEC
 406.4(D).
 4. FBC-R SECTION 314, REQUIRES THAT YOU INSTALL SMOKE
 DETECTORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  