Plan Review Notes For Permit 15030660 |
Permit Number |
15030660 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-16 16:40:37 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. YOU SHALL PROVIDE A SITE PLAN SHOWING THE LOCATION | | OF THE EXISTING METER AND MAIN DISCONNECT. | | 2. YOU SHALL PROVIDE A SITE SPECIFIC ELECTRICAL RISER | | DIAGRAM, WITH LOAD CALCS AND WIRING SCHEDULES. INCLUDE | | THE REQUIRED GROUNDING AND INTER-SYSTEM BONDING | | TERMINAL. | | 3. REPLACEMENT RECEPTACLES SHALL COMPLY WITH NEC | | 406.4(D). | | 4. FBC-R SECTION 314, REQUIRES THAT YOU INSTALL SMOKE | | DETECTORS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU | | |
|