2015-07-20 16:12:06 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE CLASSIFICATION OF WORK ON THE COVER SHEET |
| SPECIFIES THIS AS A LEVEL 1 ALTERATION. THE PLANS |
| INDICATE THAT THE SPACE HAS BEEN RECONFIGURED AND DOORS |
| AND WINDOWS HAVE BEEN ADDED OR ELIMINATED. THIS PROJECT |
| MEETS THE REQUIREMENTS FOR A LEVEL 2 ALTERATION. IF THE |
| WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF |
| THE BUILDING, THEN IT IS A LEVEL 3 ALTERATION. FBC |
| EXISTING BUILDING 401.4 |
| |
| 2) SPECIFY THE WIND DESIGN CRITERIA AND THE REQUIRED |
| DESIGN PRESSURES FOR THE (2) NEW EXTERIOR DOORS AND (1) |
| WINDOW. FBC-R301.2.1 |
| |
| 3) FBC 107.3.4 - PROVIDE TWO COMPLETE SETS OF PRODUCT |
| APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. |
| |
| 4) THE ONE SET OF PRODUCT APPROVAL INSTALLATION |
| DOCUMENTS THAT WERE SUBMITTED FOR THE JELD-WEN SLIDING |
| PATIO DOOR DOES NOT HAVE A FLORIDA PRODUCT APPROVAL FL# |
| ON THEM. SUBMIT THE COVER-SHEETS WITH THE FL#. |
| |
| 5) THE DOOR SCHEDULE ON SHEET A-200 FOR DOOR #1 |
| SPECIFIES THE DOOR TYPE AS SLIDING AND SWING DOORS ARE |
| INDICATED UNDER REMARKS FOR THIS DOOR. PRODUCT |
| APPROVALS FOR BOTH EXTERIOR DOOR TYPES WERE SUBMITTED. |
| PLEASE CLARIFY. FBC 107.2.1 |
| |
| 6) THE ENERGY FORM 402-2010 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER/AGENT. FBC ENERGY 103.2.3.2 |
| |
| 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| |
| |
| |
| |
| |