Plan Review Notes For Permit 15030623 |
Permit Number |
15030623 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-17 18:08:16 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | GAS REVIEW DENIED | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THERE IS A DISCREPANCY BETWEEN THE TANKLESS WATER | | HEATER BTUS ON THE PLANS. SHEET P-1 SPECIFIES 120,000 | | BTUS AND P-2 HAS 199,000 BTUS. SUBMIT THE | | MANUFACTURER'S SPECIFICATIONS, LISTING AND INSTALLATION | | INSTRUCTIONS FOR THE TANKLESS WATER HEATER THAT WILL BE | | INSTALLED. FBC 107.2.1 AND FBC-R G2413.2 | | | | 2) ON SHEET P-2 THE TOTAL BTU LOAD WOULD BE 279,000 | | BTUS FOR THE SUM OF 80,000 AND 199,000 BTUS. FBC | | 107.2.1 | | | | 3) USING THE LONGEST LENGTH SIZING METHOD, THE 3/4" PE | | PIPE SUPPLYING THE 199,000 BTU TANKLESS WATER HEATER IS | | TOO SMALL. AT 50 FEET THE CAPACITY IS 169,000 BTUS. | | FBC-R 2413.4.1 | | |
|