Plan Review Notes
Plan Review Notes For Permit 15030623
Permit Number 15030623
Review Stop G
Sequence Number 1
Notes
Date Text
2015-07-17 18:08:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 GAS REVIEW DENIED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS A DISCREPANCY BETWEEN THE TANKLESS WATER
 HEATER BTUS ON THE PLANS. SHEET P-1 SPECIFIES 120,000
 BTUS AND P-2 HAS 199,000 BTUS. SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS, LISTING AND INSTALLATION
 INSTRUCTIONS FOR THE TANKLESS WATER HEATER THAT WILL BE
 INSTALLED. FBC 107.2.1 AND FBC-R G2413.2
  
 2) ON SHEET P-2 THE TOTAL BTU LOAD WOULD BE 279,000
 BTUS FOR THE SUM OF 80,000 AND 199,000 BTUS. FBC
 107.2.1
  
 3) USING THE LONGEST LENGTH SIZING METHOD, THE 3/4" PE
 PIPE SUPPLYING THE 199,000 BTU TANKLESS WATER HEATER IS
 TOO SMALL. AT 50 FEET THE CAPACITY IS 169,000 BTUS.
 FBC-R 2413.4.1
  