2015-04-10 07:08:53 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| SHALL BE |
| SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| |
| 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| 3) FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE. |
| |
| 4) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 5) PROVIDE AN INTERIOR WALL SECTION OF THE WALL TO ROOF |
| EXTENSION. SPECIFY THE FRAMING MATERIAL, CONNECTIONS |
| AND FASTENERS THAT WILL BE USED. FBC 107.2.1 |
| |
| 7) PROVIDE A SECTION THROUGH THE ROOF / CEILING |
| ASSEMBLY. SHOW THE TYPE AND LOCATION OF THE INSULATION |
| THAT IS TO BE ADDED. SHOW ATTIC ATTIC ACCESS AND |
| VENTILATION. FBC 107.2.1 |
| |
| 8) REMOVE ITEMS FROM THE SCOPE OF WORK LISTED ON THE |
| PLAN THAT WILL NOT BE INCLUDED WITH THIS PERMIT. FBC |
| 107.2.1 |
| |
| 9) THE PLANS THAT WERE SUBMITTED HAVE THE TITLE BLOCK |
| OF AN ARCHITECT. FS 481 & FAC 61G1-16 REQUIRES PLANS |
| THAT ARE SUBMITTED FROM AN ARCHITECT TO HAVE THEIR SEAL |
| AND HANDWRITTEN SIGNATURE. |
| |
| IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| |