Plan Review Notes For Permit 15030536
Permit Number 15030536
Review Stop G
Sequence Number 1
Notes
Date Text
2015-03-19 10:27:281) SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION SHEETS FOR THE
 GENERATOR.THE GENERATOR SHALL BE UL2200 COMPLIANT PER
 THE FUEL GAS CODE SEC.616.1.
 2) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 THE MANUF. INSTALLATION INSTRUCTIONS AND NFPA 37. 2010
 FGC SEC.616.1.
 3) SHOW THE TERMINUS OF THE GAS VENT. THE LOCATION
 SHALL COMPLY WITH THE 2010 FGC SEC. 503.6.4, 503.8.
 4) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET
 FROM OPENINGS IN THE EXTERIOR BUILDING WALLS AND AT
 LEAST 5 FEET FROM STRUCTURES HAVING COMBUSTIBLE WALLS.
 IF THE EXTERIOR WALL IS NOT 1 HOUR FIRE RATED THEN THE
 GENERATOR SHALL BE A MIN. OF 5 FEET FROM THE EXTERIOR
 PER NFPA 37 SEC. 4.1.4.
  