2015-05-05 08:24:40 | APPROVED WITH EXCEPTION |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| 1) FBC-R - M1305.1.3 APPLIANCES IN ATTICS. ATTICS |
| CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN OPENING |
| AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO |
| ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT NOT LESS |
| THAN 30 INCHES (762 MM) HIGH AND 22 INCHES (559 MM) |
| WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG MEASURED |
| ALONG THE CENTERLINE OF THE PASSAGEWAY FROM THE OPENING |
| TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS |
| SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS |
| THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT |
| LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES (762 MM) |
| WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE APPLIANCE |
| WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING |
| DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES |
| (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL |
| OF THE LARGEST APPLIANCE. |
| 2) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS. A |
| LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| ACCORDANCE WITH CHAPTER 34. |
| |