Plan Review Notes For Permit 15030523 |
Permit Number |
15030523 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-07 15:03:36 | 1) IDENTIFY ALL THE FIXTURES ON THE SANITARY RISER. I | | CANNOT PERFORM A COMPLETE REVIEW WITHOUT THE FIXTURES | | BEING IDENTIFIED. | | 2) IT APPEARS THAT THE DESIGN OF THE RISER DOES NOT | | COMPLY WITH SEC. P3108.1 OF THE 2010 FBCR FOR THE | | REQUIREMENTS OF A HORIZONTAL WET VENT. | | 3) SUBMIT VERIFICATION THAT THE EXISTING WATER SERVICE | | IS LARGE ENOUGH TO SUPPLY THE MINIMUM REQUIRED PRESSURE | | TO ALL THE PLUMBING FIXTURES.SEC. P2903.1 & TABLE P | | 2903.2B. COUNTING UP THE FIXTURE UNITS THE WATER | | SERVICE SHALL BE A MINIMUM 1". | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|