Plan Review Notes
Plan Review Notes For Permit 15030523
Permit Number 15030523
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-07 15:03:361) IDENTIFY ALL THE FIXTURES ON THE SANITARY RISER. I
 CANNOT PERFORM A COMPLETE REVIEW WITHOUT THE FIXTURES
 BEING IDENTIFIED.
 2) IT APPEARS THAT THE DESIGN OF THE RISER DOES NOT
 COMPLY WITH SEC. P3108.1 OF THE 2010 FBCR FOR THE
 REQUIREMENTS OF A HORIZONTAL WET VENT.
 3) SUBMIT VERIFICATION THAT THE EXISTING WATER SERVICE
 IS LARGE ENOUGH TO SUPPLY THE MINIMUM REQUIRED PRESSURE
 TO ALL THE PLUMBING FIXTURES.SEC. P2903.1 & TABLE P
 2903.2B. COUNTING UP THE FIXTURE UNITS THE WATER
 SERVICE SHALL BE A MINIMUM 1".
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR