2015-04-14 10:03:38PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - SUBMIT TWO SETS OF AN ELECTRIC
 SERVICE RISER DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL
 AND GROUNDING DETAIL.
  
 2) FBC 107.3.5.3 - PROVIDE PANEL SCHEDULES AND SHOW
 CIRCUITS ON FLOOR PLAN.
  
 3) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT.
  
 4) SPECIFY THE LOCATION OF THE ELECTRICAL SERVICE ON
 THE PLANS. FBC 107.2.1
  
 5) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL EQUIPMENT ON THE PLANS.
  
 6) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 7) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
  
 8) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED. OUTDOOR OUTLET
 RECEPTACLES ARE REQUIRED TO BE GFCI PROTECTED.
  
 9) NEC 406.8 - OUTDOOR RECEPTACLES ARE REQUIRED TO BE
 WEATHER PROOF.
  
 10) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 11) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 12) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE
 OUTLET FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 13) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE
 REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE
 PLANS.
  
 14) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES
 CLOSETS SHALL BE OF THE TYPE PERMITTED AND LOCATED AS
 REQUIRED.
  
 15) FS 471 AND FAC 61G15 REQUIRES THE ENGINEER TO SIGN
 BY HAND THE LICENSEE'S HANDWRITTEN WRITTEN SIGNATURE ON
 THE PLANS. SIGNATURE STAMPS, COPIES OR OTHER FACSIMILES
 ARE NOT ACCEPTABLE.
  
  
  
  
  
  
  