2015-04-14 10:03:38 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY ELECTRIC |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC 107.3.5.3 - SUBMIT TWO SETS OF AN ELECTRIC |
| SERVICE RISER DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL |
| AND GROUNDING DETAIL. |
| |
| 2) FBC 107.3.5.3 - PROVIDE PANEL SCHEDULES AND SHOW |
| CIRCUITS ON FLOOR PLAN. |
| |
| 3) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| PRESENT. |
| |
| 4) SPECIFY THE LOCATION OF THE ELECTRICAL SERVICE ON |
| THE PLANS. FBC 107.2.1 |
| |
| 5) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE |
| ELECTRICAL EQUIPMENT ON THE PLANS. |
| |
| 6) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE |
| FOLLOWING LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| ALARMS IN THE INDIVIDUAL UNIT. |
| |
| 7) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| 10 FEET OF EACH SLEEPING ROOM. |
| |
| 8) NEC 210.8 (A) (1)-(8) - GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION REQUIRED. OUTDOOR OUTLET |
| RECEPTACLES ARE REQUIRED TO BE GFCI PROTECTED. |
| |
| 9) NEC 406.8 - OUTDOOR RECEPTACLES ARE REQUIRED TO BE |
| WEATHER PROOF. |
| |
| 10) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| PROTECTED. |
| |
| 11) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| REQUIRED. |
| |
| 12) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE |
| OUTLET FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| |
| 13) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| PLANS. |
| |
| 14) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES |
| CLOSETS SHALL BE OF THE TYPE PERMITTED AND LOCATED AS |
| REQUIRED. |
| |
| 15) FS 471 AND FAC 61G15 REQUIRES THE ENGINEER TO SIGN |
| BY HAND THE LICENSEE'S HANDWRITTEN WRITTEN SIGNATURE ON |
| THE PLANS. SIGNATURE STAMPS, COPIES OR OTHER FACSIMILES |
| ARE NOT ACCEPTABLE. |
| |
| |
| |
| |
| |
| |
| |