Date |
Text |
2015-11-18 17:33:36 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| 1. FBC-E SECTION 502.3.8: RECESSED LUMINARIES INSTALLED |
| IN THE BUILDING ENVELOPE SHALL BE IC RATED AND SEALED |
| TO LIMIT THE LEAKAGE OF AIR FROM THE CONDITIONED SPACE |
| TO THE NON-CONDITIONED SPACE. |
| 2. FBC-E SECTION 505.2 LIGHTING CONTROLS (MANDATORY): |
| YOU SHALL PROVIDE THE REQUIRED LIGHTING CONTROLS FOR |
| ROOMS 107 - 114 AND 121 - 123. THERE MAY BE ADDITIONAL |
| LOCATIONS WHICH I MAY HAVE MISSED SO REVIEW YOUR |
| LIGHTING DESIGN TO COMPLY WITH SUCH REQUIREMENT. |
| 3. FBC-E SECTION 505 ELECTRICAL POWER & LIGHTING |
| SYSTEMS (MANDATORY): HAS NUMEROUS LIGHTING REQUIREMENTS |
| WHICH MAY APPLY. |
| 4. FBC-E YOU SHALL SUBMIT INTERIOR AND EXTERIOR |
| LIGHTING POWER ALLOWANCES CHARTS INDICATING COMPLIANCE |
| WITH LIGHTING POWER ALLOWANCES. |
| 5. FBC-E 505.7.3: ALL FEEDER AND BRANCH CIRCUIT |
| CALCULATIONS SHALL TAKE INTO ACCOUNT THE CODE REQUIRED |
| VOLTAGE DROP MAXIMUMS. |
| 6. FBC-E 505.7.4 COMPLETION REQUIREMENTS: A NOTE ON THE |
| APPROVED PLANS SHALL INDICATE THAT WITHIN 30 DAYS OF |
| SYSTEM ACCEPTANCE AN AS-BUILT SET OF ELECTRICAL |
| DRAWINGS SHALL BE PROVIDED TO THE BUILDING OWNER. |
| 7. NEC 110.16: ALL ELECTRICAL PANELS AND EQUIPMENT |
| SHALL BE MARKED WITH AN ARCH-FLASH HAZARD WARNING |
| DECAL. |
| 8. NEC 210.62: THERE SHALL BE A 125 V. SINGLE PHASE 15 |
| OR 20 AMP RECEPTACLE OUTLET FOR EVERY 12 FT. OR MAJOR |
| PORTION OF SHOW WINDOW AREA MEASURED HORIZONTALLY. |
| 9. NEC 215.5: YOU SHALL SUBMIT A SITE SPECIFIC FEEDER |
| DIAGRAM SHOWING FEEDER DETAILS, LOAD CALCULATIONS, |
| CONDUCTOR SIZING AND INSULATION. THIS SHALL INCLUDE THE |
| LOAD FOR THE ADDITIONAL OUTLETS REQUIRED ABOVE. |
| 10. NEC 230: YOU SHALL INDICATE ON THE FLOOR PLAN OR |
| SITE PLAN THE LOCATION OF THE SERVICE EQUIPMENT AND ANY |
| UTILITY TRANSFORMERS. IF AUXILIARY GENERATOR IS |
| PROPOSED. MANUFACTURERS? DOCUMENTATION FOR THE |
| GENERATOR SHALL BE SUBMITTED. |
| 11. NEC 314.27(C): ALL FLOOR RECEPTACLES SHALL ME IN |
| BOXES LISTED FOR THIS PURPOSE. |
| 12. NEC 408.4: CIRCUIT DIRECTORY FOR PANEL "AC" SHALL |
| BE PROVIDED. ALL ADDITIONAL SHOW WINDOW LOADS SHALL BE |
| INCLUDED ON THE PANEL SCHEDULES. |
| 13. NEC 408.58: ALL PANELS SHALL BE MARKED WITH THEIR |
| OPERATING VOLTAGE AND PHASE DESIGNATION |
| 14. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT ACCESSIBLE |
| TO PEDESTRIANS SHALL HAVE A DEDICATED SIGN OUTLET IN AN |
| ACCESSIBLE LOCATION AT EVERY ENTRANCE ACCESSIBLE TO |
| PEDESTRIANS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |