Plan Review Notes
Plan Review Notes For Permit 15030515
Permit Number 15030515
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2016-01-28 16:39:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET A 1.3 - FOR CO PROTECTION PROVIDE CONTINUOUS
 VENTILATION PER NFPA 720.
  
 2. SHEET A 1.3 - PROVIDE INTERIOR DRAPES AND
 FURNISHINGS PROTECTION REQUIRMENTS PER NFPA 701.
  
 3. THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION
 OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE
 COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR ADDED
 CONSTRUCTION OF WALLS REQUIRES AN EVALUATION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  