Plan Review Notes For Permit 15030515 |
Permit Number |
15030515 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-01-28 16:39:55 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. SHEET A 1.3 - FOR CO PROTECTION PROVIDE CONTINUOUS | | VENTILATION PER NFPA 720. | | | | 2. SHEET A 1.3 - PROVIDE INTERIOR DRAPES AND | | FURNISHINGS PROTECTION REQUIRMENTS PER NFPA 701. | | | | 3. THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION | | OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE | | COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR ADDED | | CONSTRUCTION OF WALLS REQUIRES AN EVALUATION. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|