Plan Review Notes For Permit 15030515 |
Permit Number |
15030515 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-07-09 08:39:55 | 7/9/2015 | | PROJECT: SCHUMACHER VOLVO | | PERMIT#: 15030515 | | CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC | | , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION, | | FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN | | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | REQUIRED IN. OCCUPANCY SENSORS REQUIRED IN ACCORDANCE | | WITH PROVIDE AUTOMATIC LIGHTING SHUTOFF. FBC-ENERGY | | CODE SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. | | | | 2) RECEPTACLE OUTLET BOXES INSTALLED IN THE FLOOR SHALL | | BE LISTED SPECIFICALLY FOR THIS APPLICATION. NEC | | 314.27(C) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|