Plan Review Notes For Permit 15030515 |
Permit Number |
15030515 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-06-11 05:36:39 | 1) SHTS. P0.1 & P2.2 - AS PREVIOUSLY NOTED, THE SIZE OF | | THE NEW STORM DRAINS SHALL COMPLY WITH THE 2010 | | FBC-PLUMBING, TABLE 1106.3. THE STORM WATER ISOMETRIC | | SHOWS A TOTAL OF 3041 SQUARE FEET DRAINING INTO A 4" | | HORIZONTAL STORM WATER PIPE.EVEN AT A 4% SLOPE PER | | TABLE 1106.3, THIS LINE IS UNDERSIZED FOR A RAINFALL | | RATE OF 5 INCHES AND AN AREA OF 3041 SQUARE FEET. THE | | MINIMUM PIPE SIZE SHALL BE 6 INCHES AT A 1 % SLOPE PER | | TABLE 1106.3. THE SAME APPLIES TO THE SECONDARY | | (EMERGENCY) ROOF DRAINS. INDICATE THE SLOPE OF THE | | ELEVATED STORM DRAINAGE PIPING ON THE PLANS AND ALSO | | THE UNDERGROUND AND HORIZONTAL LINE AT GRADE.THE 6" | | HORIZONTAL LINE AT GRADE FOR THE EMERGENCY ROOF DRAINS | | AND THE LINE CONNECTING TO THE EXISTING SHALL BE | | INSTALLED WITH A MINIMUM OF A 2% SLOPE TO COMPLY WITH | | TABLE 1106.3. CLEARLY INDICATE ALL OF THE ABOVE | | APPLICABLE INFORMATION ON THE PLANS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|