Plan Review Notes For Permit 15030515 |
Permit Number |
15030515 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-27 13:27:04 | 4/27/2015 | | PROJECT: SHUMACHER VOLVO RENNOVATION | | PERMIT#: 15030515 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | COMMENTS: | | | | 1) PROVIDE A VOLTAGE DROP CALCULATION FOR BRANCH | | CIRCUIT WIRING. THE DISTANCE FROM THE PANELS IN THE | | ELECTRICAL ROOM TO THE OUTSIDE BOLLARDS AND UPLIGHTS IS | | BEYOND THE PERCENTAGE OF VOLTAGE DROP ALLOWED ON AN | | 8AMP BRANCH CIRCUIT. OPERATING AT 120VOLTS NEC | | 210.19(A) | | | | 2) PROVIDE CIRCUIT DIRECTORIES WITH EACH CIRCUIT HAVING | | A CLEAR AND SPECIFIC PURPOSE. NEC 408.4 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|