Plan Review Notes For Permit 15030511 |
Permit Number |
15030511 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-09 10:50:14 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | THE DIFFERENT WINDOW/GLASS TYPES, STRUCTURAL MULLIONS | | AND EXTERIOR DOOR TYPES. | | | | 2) R301.2.1.2 PROTECTION OF OPENINGS. WINDOWS IN | | BUILDINGS LOCATED IN WINDBORNE DEBRIS REGIONS SHALL | | HAVE GLAZED OPENINGS PROTECTED FROM WINDBORNE DEBRIS. | | GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS SHALL | | MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM | | E 1996, ASTM E 1886, SSTD 12 OR TAS 201, 202 AND 203 OR | | AAMA 506 REFERENCED THEREIN. IF STORM PANELS ARE USED | | SUBMIT TWO SETS OF PRODUCT APPROVALS, KEY PLAN AND | | INSTALLATION SCHEDULE. | | | | IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | ADDRESSED. |
|