Plan Review Notes For Permit 15030490 |
Permit Number |
15030490 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-03-16 07:54:41 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FROM PREVIOUS REVIEW: | | | | 1. FOR THE FLAT DECK, NEGATIVE DESIGN PRESURE (12'MRH, | | EXPOSURE C) FOR ZONE 3 IS -95.7. THE ASSEMBLY SELECTED | | HAS A DESIGN PRESSURE LIMITATION OF -90. FBC 2010 | | RESIDENTIAL 301 | | | | 2ND REVIEW: | | | | CONTRACTOR REQUESTED THAT: "THE W-15 SPEC SUBMITTED | | COULD BE CHANGED TO W-16". | | | | ASSEMBLY W16 IS THE ASSEMBLY SELECTED. PLEASE RESUBMIT, | | SELECTING AN ASSEMBLY WHICH MEETS THE REQUIREMENT FOR | | ZONE 3 (-95.7PSF). IF POSSIBLE, THIS WILL BE DONE AS A | | TURNAROUND. CONTRACTOR WAS ADVISED OF MY SCHEDULE. | | | | |
|