Plan Review Notes
Plan Review Notes For Permit 15030490
Permit Number 15030490
Review Stop B
Sequence Number 2
Notes
Date Text
2015-03-16 07:54:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS REVIEW:
  
 1. FOR THE FLAT DECK, NEGATIVE DESIGN PRESURE (12'MRH,
 EXPOSURE C) FOR ZONE 3 IS -95.7. THE ASSEMBLY SELECTED
 HAS A DESIGN PRESSURE LIMITATION OF -90. FBC 2010
 RESIDENTIAL 301
  
 2ND REVIEW:
  
 CONTRACTOR REQUESTED THAT: "THE W-15 SPEC SUBMITTED
 COULD BE CHANGED TO W-16".
  
 ASSEMBLY W16 IS THE ASSEMBLY SELECTED. PLEASE RESUBMIT,
 SELECTING AN ASSEMBLY WHICH MEETS THE REQUIREMENT FOR
 ZONE 3 (-95.7PSF). IF POSSIBLE, THIS WILL BE DONE AS A
 TURNAROUND. CONTRACTOR WAS ADVISED OF MY SCHEDULE.
  
  