2015-05-01 13:06:50 | 5/1/2015 |
| PROJECT: VALERO SIGN |
| PERMIT#: 15030455 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) ONE FULL SET OF PLANS WAS SIGNED OUT ON 4-9-15 PRIOR |
| TO THE RE-SUBMITTAL. THAT SET OF PLANS WAS NOT |
| RETURNED. THE RE-SUBMITTAL ONLY INCLUDES A COUPE OF |
| SEPARATE SHEETS AND IS LACKING THE ENGINEERING DESIGN |
| DOCUMENTS THAT WERE A PART OF THE ORIGINAL SUBMITTAL |
| THAT IS NO LONGER IN THE PACKAGE. |
| |
| 2) THE ELECTRICAL PLANS THAT ARE A PART OF THE |
| REMAINING SET OF PLANS IN THE PACKAGE ARE NOT SIGNED OR |
| SEALED. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN.FBC, WPB |
| AMENDMENTS 107.2.1 |
| |
| PROVIDE TWO COMPLETE SETS OF SIGNED AND SEALED DESIGN |
| DOCUMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |