 PROJECT: VELERO / CIRCLE K SIGNAGE
 PERMIT#: 15030455
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PLEASE REVISE YOUR DESIGN DOCUMENTS TO ADDRESS THE
 FOLLOWING ELECTRICAL REVIEW COMMENTS:
  
 1) NEC 600.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING,
 FIXED, MOBILE, OR PORTABLE SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3
 LISTING.
  
 2) NEC 600.6(A)(1)
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 3) FBC-ENERGY 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 4) WPB AMENDMENTS TO FBC 109.3
 PROVIDE PROOF OF OVERALL VALUE OF THE PROJECT IS
 REQUIRED AND SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ARCHITECTURAL DESIGN FEES, FABRICATION,
 STRUCTURAL, AND ELECTRICAL, PLUS OVERHEAD AND PROFIT.
 FINAL PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL. REVISE THE VALUE SUBMITTED OR SUBMIT
 SUPPORTING DOCUMENTATION INCLUDING BREAKDOWN ON
 CONTRACTS. WPB AMENDMENTS.TO FBC 109.3
  
 5) WPB AMENDMENTS TO FBC,107.2.1
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC,107.2.1, FL SS 471, 668.001-668.006
  
 6) WPB AMENDMENTS TO FBC 107.3.2
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 7) WPB AMENDMENTS FBC 107.2.1
 THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION. WPB AMENDMENTS FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  