 PROJECT: KITCHEN RENOVATION
 PERMIT#: 15030443
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. NEC 210.8(6) KITCHENS - WHERE
 THE RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP
 SURFACES.
  
 2) VERIFY OR INSTALL SMOKE DETECTORS WHERE REQUIRED IN
 THE FBC. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 4) VERIFY RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT
 NO POINT ALONG THE WALL LINE IS MORE THAN 600 MM (24
 IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.NEC 210.52(C)(1)
  