2015-05-02 12:26:10 | 4/6/2015 |
| PROJECT: KITCHEN RENOVATION |
| PERMIT#: 15030443 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| 1) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. NEC 210.8(6) KITCHENS - WHERE |
| THE RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP |
| SURFACES. |
| |
| 2) VERIFY OR INSTALL SMOKE DETECTORS WHERE REQUIRED IN |
| THE FBC. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| FBC-RESIDENTIAL 314 AND 315. |
| |
| 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 4) VERIFY RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT |
| NO POINT ALONG THE WALL LINE IS MORE THAN 600 MM (24 |
| IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| THAT SPACE.NEC 210.52(C)(1) |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |