Notes |
Date |
Text |
2015-08-28 14:28:18 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | RE-INSPECTION FEE(S). | | 1) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF INSTALLATION | | SCHEDULES AND KEY PLANS FOR THE STORM PANELS. SPECIFY | | THE OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR, | | ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL | | SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE | | APPLICABLE SECTION NUMBER FROM THE INSTALLATION | | DRAWINGS. |
|