2015-07-29 16:56:38 | PLAN REVIEW COMMENTS |
| 4TH REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS |
| MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW |
| REPLACEMENT APPLICATION IS REQUIRED. ) |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED |
| DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF |
| PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR |
| TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED |
| FOR THE SINGLE HUNG WINDOWS (NOA NO. 14-0722.07). |
| |
| 2) REPEAT COMMENT. FBC - R 301.2.1.2 SUBMIT TWO COPIES |
| OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM |
| PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES, |
| TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL |
| LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO |
| GLASS AND THE APPLICABLE SECTION NUMBER FROM THE |
| INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE |
| CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF |
| THE RELATED FORMS INCLUDING |
| THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| DEVICES. |
| HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| |
| 3) THE REVISED PLANS AND THE RESPONSE LETTER INDICATE |
| THAT THE FRONT DOOR IS TO BE LARGE MISSILE IMPACT RATED |
| TO ALLOW FOR EGRESS WHEN THE STORM PANELS ARE IN PLACE |
| DURING THE THREAT OF A STORM PER FBC - R310.4. SUBMIT |
| TWO SETS OF PRODUCT APPROVALS FOR THE 3' 0" X 6' 8" |
| IMPACT RATED FRONT DOOR THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| PRESSURES. FBC 107.3.4 |
| |
| 4) ONE SET OF PRODUCT APPROVALS WERE PREVIOUSLY |
| SUBMITTED FOR EACH OF THE FOLLOWING NON-IMPACT RATED |
| DOORS FL#16106 AND A JELD-WEN CONTOURS PREMIUM STEEL |
| WOOD EDGE HALF LITE OUTSWING DOOR WITH NO FL# INDICATED |
| ON THE DOCUMENTS. TWO SETS OF PRODUCT APPROVALS WERE |
| SUBMITTED FOR NON-IMPACT RATED DOORS (FL#15255.13) WITH |
| THE LAST RESUBMITTAL. PLEASE CLARIFY WHICH OF THESE |
| WILL BE INSTALLED. AN ADDITIONAL SET OF PRODUCT |
| APPROVALS THAT HAVE BEEN REVIEWED BY THE DESIGNER OF |
| RECORD WILL BE REQUIRED IF YOU WISH TO USE THE FIRST |
| TWO MENTIONED AND A COVER SHEET WITH THE FL# IS |
| REQUIRED FOR THE HALF LITE DOOR. FBC 107.2.1 |
| |
| 5) THE PERMIT APPLICATION IS MISSING FROM THE |
| CONSTRUCTION DOCUMENTS. A NEW REPLACEMENT APPLICATION |
| IS REQUIRED. |
| |
| 6) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |