2015-07-06 19:27:53PLAN REVIEW COMMENTS
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS
 MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW
 REPLACEMENT APPLICATION IS REQUIRED. )
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED
 DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR
 TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED
 AND TWO SETS ARE REQUIRED.
  
 2)THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 NON-IMPACT RATED WINDOWS AND GLAZED EXTERIOR DOORS.
 SUBMIT PRODUCT APPROVALS FOR THE REQUIRED IMPACT
 PROTECTION DEVICES. FBC-R301.2.1.2
  
 3) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. FBC 107.2.1 &
 FBC-R301.2.1
  
 4) FBC-R310.4 REQUIRES AT LEAST ONE MEANS OF ESCAPE TO
 BE PROVIDED WHILE STORM PANELS ARE IN PLACE DURING THE
 THREAT OF A STORM. OCCUPANTS IN ANY PART OF THE
 DWELLING SHALL BE ABLE TO ACCESS THE MEANS OF ESCAPE
 WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT UNDER THEIR
 CONTROL. SHOW COMPLIANCE.
  
  
  
  
  
  
  
  