2015-07-06 19:27:53 | PLAN REVIEW COMMENTS |
| 3RD REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS |
| MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW |
| REPLACEMENT APPLICATION IS REQUIRED. ) |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED |
| DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF |
| PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR |
| TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED |
| AND TWO SETS ARE REQUIRED. |
| |
| 2)THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| NON-IMPACT RATED WINDOWS AND GLAZED EXTERIOR DOORS. |
| SUBMIT PRODUCT APPROVALS FOR THE REQUIRED IMPACT |
| PROTECTION DEVICES. FBC-R301.2.1.2 |
| |
| 3) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. FBC 107.2.1 & |
| FBC-R301.2.1 |
| |
| 4) FBC-R310.4 REQUIRES AT LEAST ONE MEANS OF ESCAPE TO |
| BE PROVIDED WHILE STORM PANELS ARE IN PLACE DURING THE |
| THREAT OF A STORM. OCCUPANTS IN ANY PART OF THE |
| DWELLING SHALL BE ABLE TO ACCESS THE MEANS OF ESCAPE |
| WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT UNDER THEIR |
| CONTROL. SHOW COMPLIANCE. |
| |
| |
| |
| |
| |
| |
| |
| |