Plan Review Notes
Plan Review Notes For Permit 15030431
Permit Number 15030431
Review Stop M
Sequence Number 2
Notes
Date Text
2015-05-26 11:37:59PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. THE MECHANICAL
 EQUIPMENT LISTED IN THE SCHEDULE ON SHEET 3 IS REQUIRED
 TO MATCH THE SIZING CALCULATIONS.
 NEW COMMENT. THE EQUIPMENT SCHEDULE ON SHEET 3 OF THE
 PLANS DOES NOT MATCH THE ONE SPECIFIED IN THE SIZING
 CALCULATIONS. THE PLAN SPECIFIES A TRANE WITH A 14.5
 SEER AND THE LOAD CALCS. HAVE A GOODMAN, JANITROL,
 AMANA DISTI... WITH A 16 SEER. THE EQUIPMENT SCHEDULE
 COLUMN HEADER FOR SEER HAS 16 SEER WITH 14.5 LISTED AS
 THE SEER FOR THE TRANE UNIT.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. SPECIFY THE SIZES OF THE RETURN AIR TRANSFER
 GRILLS ON THE MECHANICAL PLAN. TRANSFER GRILLES SHALL
 USE 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF
 SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER
 GRILLES AND USING AN UNRESTRICTED 1 INCH UNDERCUTTING
 OF DOORS TO ACHIEVE PROPER RETURN AIR BALANCE.
 HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
 NEW COMMENT. SHEET 3 OF THE PLANS SPECIFIES 8 X 8
 TRANSFER GRILLS (64 SQUARE INCHES) WHICH IS ONLY ENOUGH
 FOR 128 CFM. ALL OF THE BEDROOMS HAVE MORE CFMS THAN
 THIS.
  
 3) NEW COMMENT. THERE IS ANOTHER MECHANICAL PLAN
 INCLUDED WITH THE ENERGY CALCULATIONS THAT DOES NOT
 MATCH THE ONE ON SHEET 3 OF THE PLANS. THE FOLLOWING
 COMMENTS ADDRESS THAT DRAWING. THERE IS NO EQUIPMENT
 SCHEDULE, THE SIZE OF THE SUPPLY GRILLS ARE NOT
 SPECIFIED, THE SIZE OF THE RETURN GRILL IN THE HALLWAY
 IS NOT SPECIFIED, THE SIZE OF THE RETURN TRANSFER DUCTS
 AT BEDROOMS 1 AND 2 ARE NOT SPECIFIED AND THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 REMOVE THE MECHANICAL PLANS THAT WILL NOT BE USED. FBC
 107.2.1
  
  