2015-05-26 07:31:03 | PLAN REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY ELECTRICAL |
| THE FOLLOWING COMMENTS FROM THE 1ST REVIEW WERE NOT |
| ADDRESSED. PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| THAT SPACE. |
| |
| 2) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP |
| SURFACES ARE REQUIRED TO BE GFCI PROTECTED. |
| |
| 3) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| PROTECTED. |
| |
| 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| REQUIRED. |
| |
| 5) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| PLANS. |
| |
| 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| |
| 7) THE CONDUIT AND WIRE SIZE FOR THE WEATHER HEAD SHOWN |
| ON THE SERVICE RISER PLAN IS INCORRECT. NEC 310.15 (B) |
| (6). |
| |
| 8) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| R314.3 LOCATION. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| ALARMS IN THE INDIVIDUAL UNIT. |
| |
| 9) SPECIFY THE LOCATION OF THE ELECTRIC METER AND |
| PANELS ON THE PLANS. FBC 107.2.1 |
| |
| 10) THE LUMINAIRES LOCATED IN THE BEDROOM CLOSETS SHALL |
| MEET THE REQUIREMENTS OF NEC 410. |
| |
| 11) FBC 107.2.1 - INFORMATION ON CONSTRUCTION |
| DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. THIS ITEM WAS |
| ADDRESSED. PLANS WERE SIGNED AND SEALED BY A FLORIDA |
| LICENSED ENGINEER. |
| |
| 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| |
| |