Plan Review Notes
Plan Review Notes For Permit 15030431
Permit Number 15030431
Review Stop B
Sequence Number 2
Notes
Date Text
2015-05-26 10:17:31PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION AND
 OLD PLANS ARE MISSING FROM THIS RESUBMITTAL. )
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEW COMMENT. BASED ON YOUR RESPOSE TO THE PREVIOUS
 COMMENT, YOU INTEND TO BRING THE ILLEGALLY ENCLOSED
 PORCHES INTO CODE COMPLIANCE. SUBMIT TWO COPIES OF
 ENERGY CALCULATIONS TO SHOW THAT THE ENCLOSED PORCHES
 COMPLY WITH THE 2010 FBC ENERGY CONSERVATION AND SEE
 THE IMPACT FEE REVIEW STOP.
  
 2) REPEAT COMMENT. THE VALUE OF $7500.00 SPECIFIED ON
 THE APPLICATION IS LOW FOR THE WORK SHOWN ON THE PLANS.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT DOORS
 AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES.
 NEW COMMENT. THE PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE FOR NON-IMPACT RATED WINDOWS AND GLAZED EXTERIOR
 DOORS. IF YOU WILL BE INSTALLING NON-IMPACT WINDOWS AND
 DOORS, REVISE THE PLAN NOTES AND SUBMIT PRODUCT
 APPROVALS FOR THE REQUIRED IMPACT PROTECTION
  
 4) REPEAT COMMENT. SHOW COMPLIANCE WITH FBC R311.7.7
 AND R312 FOR GUARDS AND HANDRAILS ON THE DECK STAIRS.
 NEW COMMENT.THE PLAN SPECIFIES THAT THE STAIRS HAVE 6
 RISERS. FBC-R311.7.7 REQUIRES HANDRAILS NOT LESS THAN
 34 INCHES OR MORE THAN 38 INCHES ON AT LEAST ONE SIDE
 OF A FLIGHT OF STAIRS WITH FOUR OR MORE RISERS.
  
 5) REPEAT COMMENT. SHOW COMPLIANCE WITH FBC-R314.3.1
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 NEW COMMENT. IN ADDITION TO THE SMOKE ALARMS REQUIRED
 IN EACH SLEEPING ROOM, THEY ARE REQUIRED OUTSIDE EACH
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS.
  
 6) NEW COMMENT. THE TYPICAL EXTERIOR WALL SECTION ON
 SHEET 5 SPECIFIES 6" BATT INSULATION WITH AN R-30 MIN.
 INSULATION VALUE. THERE ARE NOT ANY 6 INCH THICK BATT
 INSULATIONS THAT CAN PROVIDE A R-30 THERMAL RESISTANCE.
 DEPENDING ON THE INSULATING MATERIAL USED, THE
 THICKNESS REQUIRED TO ACHIEVE R-30 VARIES. YOU CAN
 REVISE NOTE TO SAY MINIMUM R-30 BATT INSULATION. FBC
 107.2.1
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  