2015-04-13 14:31:24PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. THE MECHANICAL
 EQUIPMENT LISTED IN THE SCHEDULE ON SHEET 3 IS REQUIRED
 TO MATCH THE SIZING CALCULATIONS.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. SPECIFY THE SIZES OF THE RETURN AIR TRANSFER
 GRILLS ON THE MECHANICAL PLAN. TRANSFER GRILLES SHALL
 USE 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF
 SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER
 GRILLES AND USING AN UNRESTRICTED 1 INCH UNDERCUTTING
 OF DOORS TO ACHIEVE PROPER RETURN AIR BALANCE.
 HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) THE PLANS SHOW THE AIRHANDLER LOCATED IN A CLOSET.
 IF THE RETURN IS THROUGH A LOUVERED DOOR, SPECIFY THAT
 ON THE PLANS. FBC 107.2
  
  