2015-04-13 17:12:52PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 2) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP
 SURFACES ARE REQUIRED TO BE GFCI PROTECTED.
  
 3) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 5) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE
 REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE
 PLANS.
  
 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 7) THE CONDUIT AND WIRE SIZE FOR THE WEATHER HEAD SHOWN
 ON THE SERVICE RISER PLAN IS INCORRECT. NEC 310.15 (B)
 (6).
  
 8) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 9) SPECIFY THE LOCATION OF THE ELECTRIC METER ON THE
 PLANS. FBC 107.2.1
  
 10) THE LUMINAIRES LOCATED IN THE BEDROOM CLOSETS SHALL
 MEET THE REQUIREMENTS OF NEC 410.
  
 11) FBC 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  