2015-04-10 11:25:10 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) ACCORDING TO THE PALM BEACH COUNTY PROPERTY |
| APPRAISER THE MASTER BEDROOM, BATHROOM NO. 1 AND FOYER |
| ARE EITHER ENCLOSED OR OPEN PORCHES AND NOT CONSIDERED |
| HABITABLE SPACE. YOU WILL NEED TO SUBMIT DOCUMENTATION |
| TO SHOW THAT THE PORCHES WERE LEGALLY CONVERTED WITH |
| THE PROPER PERMITS AND INSPECTIONS. OTHERWISE, YOU WILL |
| HAVE TWO OPTIONS EITHER CONVERT THE AREAS BACK TO |
| PORCHES OR BRING THEM INTO COMPLIANCE WITH THE 2010 |
| FLORIDA BUILDING CODE AND 2008 NATIONAL ELECTRICAL |
| CODE. UNDER THE 2010 FBC EXISTING BUILDING THIS IS |
| CONSIDERED A CHANGE OF OCCUPANCY WITHOUT A CHANGE OF |
| OCCUPANCY CLASSIFICATION. IN ORDER FOR THESE AREAS TO |
| BE BROUGHT INTO COMPLIANCE, THEY WILL BE REQUIRED TO |
| COMPLY WITH CHAPTER 9 OF THE 2010 FBC EXISTING |
| BUILDING. THE FOLLOWING ITEMS WILL BE REQUIRED TO BE |
| MADE CODE COMPLIANT. THE STRUCTURE IN THESE AREAS ARE |
| REQUIRED TO MEET THE WINDLOAD REQUIREMENTS FOR THE |
| BUILDING ENVELOPE ( IN ADDITION TO GRAVITY LOADS), |
| PRODUCT APPROVALS FOR EXTERIOR DOORS AND WINDOWS, |
| EGRESS REQUIREMENTS, LIGHT AND VENTILATION, SMOKE AND |
| CARBON MONOXIDE ALARMS, FIRE SEPARATION REQUIREMENTS ( |
| SEPARATION DISTANCE AND ALLOWABLE OPENINGS), THE |
| REQUIREMENTS OF THE 2010 FBC ENERGY CONSERVATION, 2010 |
| FBCR MECHANICAL, THE REQUIREMENTS OF THE 2010 FBCR |
| PLUMBING AND THE ELECTRICAL SYSTEM IS REQUIRED TO |
| COMPLY WITH THE 2008 NATIONAL ELECTRIC CODE. THE PLANS |
| ARE REQUIRED TO BE REVIEWED BY PLAM BEACH COUNTY TO |
| DETERMINE IF IMPACT FEES ARE DUE. SPECIFY THE SQUARE |
| FOOTAGE OT THE EXISTING CONDITIONED SPACE AND THE |
| UNCONDITIONED SPACE (ILLEGALLY CONVERTED) ON THE PLANS. |
| |
| 2) THE VALUE OF $7500.00 SPECIFIED ON THE APPLICATION |
| IS LOW FOR THE WORK SHOWN ON THE PLANS. FBC 109.3 |
| BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 3) THE PLANS HAVE AN ENGINEER'S TITLE BLOCK AND ARE |
| REQUIRED BY FS 471 & FAC 61G15 TO HAVE HIS SEAL AND |
| HANDWRITTEN SIGNATURE ON THEM. |
| |
| 4) THE PLANS SPECIFY NEW IMPACT DOORS AND WINDOWS. FBC |
| 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR |
| THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, |
| STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. |
| |
| 5) SPECIFY THE TYPES AND SIZES OF THE WINDOWS THAT WILL |
| BE REPLACED. EXISTING BEDROOM EMERGENCY ESCAPE AND |
| RESCUE WINDOWS ARE REQUIRED TO COMPLY WITH FBC EXISTING |
| BUILDING 604.1 MEANS OF EGRESS FOR BUILDINGS UNDERGOING |
| ALTERATION SHALL COMPLY WITH THE REQUIREMENTS OF |
| SECTION 601.1 AND THE SCOPING PROVISIONS OF CHAPTER 1 |
| WHERE APPLICABLE. EXCEPTION: DOOR AND WINDOW |
| DIMENSIONS. IN RESIDENTIAL DWELLINGS AND DWELLING |
| UNITS, A MAXIMUM OF 5 PERCENT REDUCTION IN THE CLEAR |
| OPENING DIMENSIONS OF REPLACEMENT DOORS AND WINDOWS |
| SHALL BE ALLOWED. |
| |
| 6) THERE IS CONFLICTING INFORMATION ON SHEET 5. THE |
| EXTERIOR WALL SECTION SPECIFIES A WOOD FRAME WALL ON A |
| MONOLITHIC CONCRETE SLAB. THE DECK PLAN INDICATES THAT |
| THE EXISTING EXTERIOR WALL IS CBS AND PROBABLY HAS A |
| CRAWL SPACE SINCE THE DECK IS 3 FEET OFF THE GROUND. |
| PLEASE CLARIFY. FBC 107.2.1 |
| |
| 7) SHOW COMPLIANCE WITH FBC R311.7.7 AND R312 FOR |
| GUARDS AND HANDRAILS ON THE DECK STAIRS. |
| |
| 8) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| THE 2 X 8 JOISTS TO THE 2 X 10 BEAMS AND 2 X 6 LEDGERS |
| AND THE 2 X 10 BEAMS TO THE 2 X 6 LEDGERS TO PROVIDE A |
| CONTINOUS LOAD PATH REQUIRED BY FBC-R 301.1 . |
| |
| 9) SPECIFY THE REQUIRED LIVE LOADS FOR THE PORCH ON THE |
| PROPOSED DECK ON THE PLANS. FBC-R301.5 |
| |
| 10) SHOW COMPLIANCE WITH FBC-R314.3.1 WHEN ALTERATIONS, |
| REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| NEW DWELLINGS. |
| |
| 11) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |